Building regulations - fire safety and compliance call for evidence: analysis of responses
This analysis of consultation responses will help inform Scottish Government policy decisions in response to the Grenfell Tower Inquiry Phase 2 recommendations, including wider changes to Scottish Building Standards, fire safety regulations and guidance, and the compliance plan approach.
4. Rate of fire spread and means of escape for vulnerable and disabled people
Recommendation 8 of the Grenfell Tower Inquiry Phase 2 report highlights the need to make an essential part of any fire safety strategy the calculation of the likely rate of fire spread and the time required for evacuation, including the evacuation of those with physical or mental impairments.
At present, there are no provisions specific to domestic buildings which mandate the production of a fire safety strategy. A fire safety design summary (FSDS) is sought for new non-domestic buildings.
The Call for Evidence document sets out UK government regulations relating to residential evacuations, noting that these mandate building emergency evacuation plans in these buildings. In Scotland, recommendation 57 asks that consideration be given to personal emergency evacuation plans.
Q5a. Do you consider current guidance on escape for vulnerable and disabled people to be effective and up to date?
| Respondent type | Sample size (n=) | % Yes | % No | % Not sure | % No answer |
|---|---|---|---|---|---|
| All respondents | 57 | 2 | 51 | 25 | 23 |
| All answering | 44 | 2 | 66 | 32 | - |
| Individuals | 8 | 13 | 75 | 13 | - |
| Organisations: | 36 | 0 | 64 | 36 | - |
| - Trade Association | 6 | 0 | 83 | 17 | - |
| - Local Authority | 7 | 0 | 57 | 43 | - |
| - Professional Body | 4 | 0 | 75 | 25 | - |
| - Consultancy | 5 | 0 | 100 | 0 | - |
| - Construction Industry | 3 | 0 | 0 | 100 | - |
| - Manufacturer | 2 | 0 | 100 | 0 | - |
| - Housing Provider / RSL | 2 | 0 | 100 | 0 | - |
| - Other | 7 | 0 | 29 | 71 | - |
Among those answering Q5a, two thirds (66%) disagreed that guidance on escape for vulnerable and disabled people is effective and up to date, while 2% agreed and 32% were unsure. While 13% of individuals felt it is effective and up to date, no organisations held this view, with 64% of organisations disagreeing and 36% unsure. Disagreement was most prevalent in most organisation types, but all construction industry organisations and 71% of other organisations that answered were unsure.
Over six in ten respondents left an open comment at Q5a. The most prevalent themes were that the guidance was not sufficiently effective or up to date, suggestions to improve the guidance and issues with refuge areas / Stay Put strategy.
Guidance is not sufficiently effective or up to date
Many respondents felt that the guidance was not sufficiently effective or up to date, particularly for taller buildings, for instance, that it was not sufficiently clear or detailed enough. Points raised included that:
- Guidance is not suitable for multi-storey domestic buildings, as the current FRA framework does not specify how the assessor should identify, plan for or record provision for vulnerable and disabled occupants affecting their ability to self-evacuate.
- No guidance for the Responsible Person is given on what ‘adequate means of escape’ means in practice in a traditional multi-storey building with a single staircase and complex internal layout.
- Many responsibilities relating to the evacuation of vulnerable and disabled people fall under building management, yet these duties are not routinely monitored, enforced or verified.
- While the DTH provides general principles, it does not set out clear or consistent expectations on how designers should consider assisted evacuation.
- Guidance for buildings under 11m indicates combustible facade materials can be used.
- Section 2 does not set out a clear expectation that designers should consider independent evacuation for people with different types of disability, not just mobility impairment.
- It does not reflect the demographic reality of an ageing population with increasing levels of mobility, sensory or cognitive impairment.
- There was insufficient guidance on the extended time taken for escape by vulnerable and disabled occupants.
“This is not a theoretical risk. Scotland's city centre Victorian commercial stock is occupied at upper floors by a range of uses — offices, residential above commercial, short-term let accommodation, hospitality — that include occupants who may have mobility impairments and who may not be known to the building manager. The cross-tenancy coordination protocol proposed in prior submissions to this Call for Evidence is the appropriate vehicle for addressing this gap in the non-domestic multi-occupancy context: annual landlord-to-tenant communication should include identification of any occupants who would require assistance to evacuate and documentation of individual arrangements for their evacuation.” – Organisation
“At present, there is limited clarity in the guidance on how these considerations should be addressed in practice. While general principles are included, there is a lack of specific direction, particularly in relation to different categories of occupants, building types and tenures.” - Homes for Scotland
Suggested improvements to the guidance
Given the issues raised in the theme above, several respondents commented on ways the guidance could be improved. More improvements to the DTH were felt to be needed compared to the NDTH. Suggestions included that guidance should:
- Provide more explicit requirements for assessing risk, time to evacuation, and building performance in relation to occupants who may not be able to self-evacuate.
- Give more explicit direction on factors like smoke control in evacuation routes, resilience of power supplies, and periodic revalidation of systems.
- Be strengthened to require A2-s1, d0 or better external wall materials in the external walls of all buildings accommodating vulnerable or disabled occupants, regardless of height.
- Have clearer expectations of designers to meet the standards, encouraging inclusive design and reducing reliance on management controls.
- Introduce specific clauses in Section 2 (for example, 2.9, 2.11, etc.) so each standard considers how all occupants are intended to escape, where practicable, without assistance.
- Reflect current housing models, demographic change, and the increasing complexity of resident needs, e.g. tighten up on whether suppression to common closes should be provided to avoid assumptions that residents have no vulnerabilities.
- Give increased clarity over the definitions of ‘vulnerability’ and ‘disability’ as these can be wide-ranging.
- Consider whether further measures are needed to protect the person in the room of the fire origin.
- Consider recent research findings that discuss alerting more vulnerable members of society (details not provided).
- Be reviewed regarding disabled escape, particularly regarding gallery floors.
- Consider referencing the Scottish Government document ‘Practical Fire Safety Guidance – The evacuation of disabled persons from buildings’.
“A clearer national direction is required on managing evacuation risk in unstaffed accommodation, thresholds for when continued occupation becomes unsafe, and the respective roles of housing, Building Standards, and adult support and protection processes in supporting safe outcomes for vulnerable and disabled residents.” - Aberdeenshire Council - Building Standards
Issues with Refuge areas / Stay Put strategy
A range of points were made by some respondents regarding refuge areas. These are places where disabled people can wait in the event of a fire until fire and rescue services can evacuate them. As the guidance on passive vs. active escape was felt to assume vulnerable and disabled residents can wait for manual rescue in buildings with high-speed fire spread risks, it was considered not to be effective.
Evidence from the Glasgow Union Street fire and the Grenfell Tower Inquiry found that where compartmentation is compromised, a refuge area can become a trap rather than a place of safety. Evacuation in such circumstances can become more complex, hazardous and less predictable. For instance, high fatality rates among disabled people in the Grenfell Tower fire were highlighted by one respondent. Where compartmentation is compromised, another respondent noted escape routes must remain clear of smoke while a more arduous evacuation is attempted.
One respondent stated they were aware of examples of building designs that provided minimal refuge spaces for vulnerable people, rather than properly integrated evacuation strategies and systems. Another felt it was unclear how Standard 2.9 requires that necessary provisions be available for all occupants to allow them to escape safely, given that the fire service cannot be relied on to assist with evacuation. This was considered to place the onus on fire engineers to ensure compliance, which was felt to be inappropriate.
“Assumptions around evacuation time, assistance availability, and the continued viability of Stay Put strategies are often implicit rather than explicitly assessed. In practice, this can lead to a mismatch between design assumptions and the realities of occupant capability, building management arrangements, and emergency response conditions.”- Individual
Suggested improvements to the guidance in this area included:
- Recognising that Stay Put is only viable when escape routes are clear of smoke.
- Consider introducing provisions for temporary waiting spaces and emergency voice communication systems in flatted developments.
- Taking account of 2024/25 BSR research by OFR Consultants that categorised evacuation lifts as a “++” impact intervention, providing they are far more effective at reducing both total evacuation time and physical strain on the Fire and Rescue Services.
- Recognising that refuge spaces are not only for those with limited mobility, but also for those with cognitive and sensory disabilities.
- Requiring detection in escape routes for Carbon Monoxide alongside forms of toxic smoke that impair visibility as part of an alert system to help provide real-time information to the attending Fire and Rescue Services.
- Include guidance on the provision and location of refuges and how to protect them, e.g. located in fire-protected or ventilated lobbies.
- Refer to BS 9792: 2025 on FRAs.
- Being clear as to how Standard 2.9 could reasonably be complied with.
Personal emergency evacuation plans (PEEPs)
Some respondents noted there is currently no mandatory framework for PEEPs in domestic settings in Scotland. Views included that this left a ‘responsibility vacuum’ between the designer and eventual building owner, that it created an L4 Operational Process failure in the regulatory system and created inconsistent implementation of PEEPs.
One respondent noted that evacuation strategies should be appropriately recognised as being tailored to individual needs and that support requirements can change over time. However, they felt that this assumed a level of staffing, oversight or practical control that did not reflect the reality of many housing models in use across Scotland, particularly in general needs supported housing that operates without staff on site 24 hours a day. Another highlighted that the Grenfell Tower Inquiry found that building management had no mechanism for identifying disabled people who could not self-evacuate, no individual evaluation plans were prepared and a lack of shared information about the location and mobility needs of vulnerable residents with the London Fire Brigade before the fire.
“The question is not whether Scotland should introduce PEEP or equivalent provisions — the Phase 2 Report, the Phase 1 Report, the English Regulations, and the Grenfell evidence all establish that it should. The question is how Scotland designs that provision to be more effective than the English equivalent, which disability advocacy organisations including Disability Rights UK and Inclusion London have characterised as insufficiently robust in its current form, particularly regarding the consent-based approach to resident participation and the absence of a specific obligation to share information with fire and rescue services without resident consent in emergency circumstances.” – Organisation
“Significant gaps exist due to inconsistent implementation of PEEPs, outdated or missing resident data, and limited prioritisation by building managers, which undermine evacuation planning. As a result, the guidance is not yet reliably operationalised and requires better enforcement, coordination, and data management to be effective.” - University of Lancashire
BS 9991: 2024
Some respondents highlighted BS 9991: 2024 as a relevant standard to adopt, with calls for the DTH to reference it explicitly and to draw out its provisions on evacuation for residents with mobility impairments as minimum standards for FRA assessment. A few of these respondents noted the recent changes to BS 9991 (and BS EN 81-76: 2025) that included the most up to date guidance on evacuation lifts.
Roles and responsibilities
The need for guidance to better reflect the role of certain people who may be involved in the evacuation of vulnerable and disabled people was mentioned by some respondents, notably, building owners, housing providers, e.g. managers, health, social care partners and families. One respondent, however, felt that RSLs do not consider it their role to provide personal guidance to tenants living in older properties.
Other comments
A few respondents the guidance should be reviewed for existing buildings. Clarity was sought on alternative measures, for instance, where layout constrained evacuation.
One respondent noted consideration is being given to the role FSDS could play in this regard; however, they were uncertain as to the benefits these provide either to SFRS or the building owner.
Q5b. Is the current guidance easy to understand and consistently applied?
| Respondent type | Sample size (n=) | % Yes | % No | % Not sure | % No answer |
|---|---|---|---|---|---|
| All respondents | 57 | 12 | 35 | 23 | 30 |
| All answering | 40 | 18 | 50 | 33 | - |
| Individuals | 8 | 0 | 75 | 25 | - |
| Organisations: | 32 | 22 | 44 | 34 | - |
| - Trade Association | 6 | 0 | 67 | 33 | - |
| - Local Authority | 7 | 71 | 14 | 14 | - |
| - Professional Body | 3 | 67 | 33 | 0 | - |
| - Consultancy | 4 | 0 | 100 | 0 | - |
| - Construction Industry | 3 | 0 | 0 | 100 | - |
| - Manufacturer | 2 | 0 | 50 | 50 | - |
| - Housing Provider / RSL | 2 | 0 | 50 | 50 | - |
| - Other | 5 | 0 | 40 | 60 | - |
Half (50%) of those answering Q5b disagreed that the guidance is easy to understand and consistently applied, while 18% agreed it is, and 33% were not sure. Agreement with this question was driven by local authorities and professional bodies that answered, with 71% and 67%, respectively, agreeing. Among organisations overall, however, 44% disagreed, 22% agreed, and 34% were unsure, with mixed views noted by organisation type.
Almost half of respondents left an open comment at Q5b. Most commonly, expressed views indicated that the guidance was not easy to understand nor consistently applied. This section addresses those who disagree first, followed by those who agree.
No, it is not easy to understand or consistently applied
The guidance was not felt to be sufficiently easy to understand or consistently applied, according to several respondents. A lack of clarity in the guidance or insufficient detail were issues identified that could lead to variable understanding and inconsistent application according to these respondents. Reasons for these views included:
- The guidance relies on high level assumptions rather than defined methodologies.
- Key elements such as expectations around escape for residents who cannot self-evacuate are not explicitly defined.
- A lack of standardised approaches to calculating evacuation time and fire spread in relation to vulnerable occupants.
- Too great a focus on prescriptive minimums rather than comprehensive, performance-based solutions with evidence of practice examples where building designs provided only minimal refuge spaces rather than properly integrated evacuation strategies and systems.
- Significant verifier differences in interpretation over refuges, evacuation lifts and management procedures.
Areas where clarity and greater standardisation was recommended were in definitions of vulnerable and disabled occupants, methodologies, means of escape, smoke control in evacuation routes, resilience of power supplies and periodic revalidation of systems. For instance, one respondent felt improvements in clarity, structure and prescriptiveness were needed, especially in safety-critical areas.
Similarly, some other respondents felt the guidance was not well understood, again due to a lack of clarity in the guidance and different interpretations causing confusion among stakeholders.
“Currently, the application of the Technical Handbook can lead to highly variable outcomes as it is not clear or easy for industry or regulators to understand, interpret, or apply and does not provide sufficient clarity on the minimum competency requirements for those responsible for its use. The guidance should enhance the clarity, logical structure, and prescriptiveness of key sections - particularly those relating to safety-critical issues – in order to significantly improve usability and enforcement and reduce the risk of misinterpretation.” - Mineral Wool Insulation Manufacturers Association (MIMA)
“Technical Ambiguity: While BS 9991:2024 provides a code of practice, the Technical Handbooks do not yet provide a "clear and conservative" methodology for calculating RSET (Required Safe Egress Time) for impaired occupants.” - Individual
Yes, the guidance is easy to understand and consistently applied
Some respondents agreed that the guidance was easy to understand and consistently applied, with two noting this in general terms. One qualified their view by stating that while clear and understood it was limited in scope and application.
“Rate of fire spread and means of escape is consistently applied to the relevant building types as set out in the technical guidance. In practice, the principles relating to fire growth, containment, and evacuation strategy are implemented in a uniform way across the applicable building categories, reflecting the intent of the Technical Handbooks.” - Aberdeenshire Council - Building Standards
Q5c. What improvements or changes are needed in this area?
Four in ten respondents left an open comment at Q5c with a wide range of suggested improvements or changes identified. The most prevalent themes were aspects of the guidance to update, to improve guidance on evacuation lifts, PEEPs and FSDSs.
Aspects of the guidance to update
The need to update and review the guidance was highlighted by several respondents. Including more examples was mentioned at Q5c and raised by a small number of respondents at Q5b. A few respondents specifically mentioned the need to update the guidance at this point on vulnerable and disabled people, such as requiring fire suppression where vulnerable people may use the building, recognising that heavy doors and automatic closing devices can be problematic for these individuals and emphasising the need to validate the resilience and reliability of fire safety controls and power supplies.
Other views included:
- A few respondents who felt that more attention should be paid to consistency, such as a review of language to ensure clarity of understanding of descriptions.
- Two respondents who felt the guidance should clearly address smoke control, such as giving more attention to the need for existing buildings to prevent smoke spread through compartmentation and providing a clear, simplified methodology for designers to prove that the time taken to alert and evacuate a vulnerable person is lower than the time it takes for smoke to compromise the escape route.
- Two respondents who suggested a new annex that explicitly addresses issues such as assisted evacuation, refuge arrangements and associated alarm or detection provisions.
- Requiring identification of any regular occupants who would require assistance to evacuate.
- Making compulsory Owners Associations legally responsible for maintaining the ‘Golden Thread’ of fire safety information, including the management of evacuation lifts and resident PEEPs.
- Commission or incorporate emerging research into the effectiveness of FSDS to establish their effectiveness in supporting building safety.
- Requiring implementation of clearer communication and resident engagement, with simplified guidance, regularly communicated and provided in accessible formats.
- Introducing a requirement to define the use of a building to assist verifiers.
- Better integration between fire safety, access and conservation.
- Consideration of domestic care environments.
- Mandating periodic revalidation and testing of fire safety systems under the proposed CPA to verify ongoing performance.
- Greater emphasis on practical training, multi-agency coordination and adoption of technologies (e.g. evacuation alert systems).
Some other respondents felt aspects of the guidance should be clearer, such as clarifying:
- The classification of vulnerable tenants.
- Defining ‘reasonable adjustments’ for existing buildings.
- Being explicit on acceptable design solutions and evidence requirements.
- The limits of operational management.
- Clear expectations for any staff and building operators.
- The fire alarm systems to be used.
“In certain types of flatted blocks, we have common rooms to promote interaction between residents. Clarity on the fire alarm system to be used in this scenario would be useful. Typically, there is a stay put policy in place when in your dwelling but, if you are in the common room, what is expected? Do you escape to a place of safety or head back to your own dwelling and stay put?” - West of Scotland Housing Association
Evacuation lifts
Some respondents specifically mentioned evacuation lifts. Views on this included:
- Two respondents who felt BS 9991: 2024 should be explicitly referenced, and guidance amended to require at least one evacuation lift per escape stairway for all new residential buildings over 11m to remove the ‘blockage’ effect on stairs.
- To clearly define performance expectations, reliability requirements and maintenance responsibilities when evacuation lifts or other assisted escape measures are proposed.
- To be clearer on the circumstances in which evacuation lifts should be provided alongside any necessary supporting fire-protected lobbies and shafts.
- To require that any building warrant application for a high-rise residential or high risk non-domestic building addresses evacuation lift provision for non-ambulant occupants as part of the fire safety design.
PEEPs
Improved guidance on PEEPs was recommended by some respondents at 5c, and a few at Q5b incorporated here. Views included:
- Including specific guidance on the production of PEEPs for high-rise residential buildings.
- Making PEEPs mandatory for residents with physical or mental impairments and to have them form part of an emergency evacuation plan for the whole building.
- The need for clearer guidance on PEEPs for housing, particularly for HRBs.
- More consistent use of Premises Information Boxes and PEEPs, with accurate, up to date information on vulnerable residents.
- Adopting a person-centred approach for buildings housing vulnerable occupants, including in healthcare, care and supporting living settings.
- Adopting clear legal structures and operational responsibility to support person-centred risk assessments.
Design solutions / scenarios
Some respondents commented on the need to improve guidance to assist design or for the benefit of designers. These views included requiring more explicit design stage assessment of evacuation time and occupant vulnerability, ensuring guidance recommendations set out how designers can comply with Standard 2.9 and clearer expectations of inclusive design.
Management approaches
Comments on building management, given its role in promoting fire safety, were raised by a few respondents. These views included:
- That buildings did not have 24/7 management to assist with fire safety.
- A need to reduce reliance on management controls.
- Requiring post-completion checks or a formal process for notifying changes in occupancy type.
- Strengthening building management responsibilities and oversight.
“There is no ongoing requirement for checks of flatted buildings with multiple owners, how may change aspects of the building effectively reducing the fore compartmentalisation. Such as installing a new front door which doesn’t meet the required fire resistance. Should changes be undertaken without permission to the required standards who would know and if they did what action could be taken to ensure the integrity of the entire building.” - Aberdeenshire Council - Building Standards
Refuge spaces
A few respondents called for either the policy of refuge spaces to be reviewed or for improved guidance in this area. Two respondents expressed the view that refuge spaces could not be relied on, with one suggesting the guidance should make it explicit that such provision is only effective when a functioning individual evacuation plan exists that defines who will assist the occupant, with what equipment, and in what timeframe.
“The 2026 Union Street fire and the 2025 Madrid tragedy demonstrate that in complex or high-hazard buildings, the 'Available Safe Egress Time' is rapidly shrinking. We cannot continue to rely on 'Refuge Areas' where vulnerable people wait for an overstretched Fire Service. We must move toward the English model of Evacuation Shafts (protected stair + lift + lobby) to ensure that equality of escape is a physical reality, not just a policy ambition.” - Individual
Other views
Some respondents felt the guidance on FSDS should be improved; their views have been incorporated at Q6a. A few felt considerations should be given to how measures can be incorporated for specific situations, e.g. retrofits or refurbishments of existing buildings, historic typologies, or small non-domestic buildings, where provision is challenging.
One respondent felt there should be a focus on introducing a clearer, standardised approach to assessing the rate of fire spread grounded in conservative assumptions and transparent methodologies rather than optimistic scenarios. They felt the approach should address alerting time and evacuation time, including explicit consideration of occupants who may require assistance.